Erosion–corrosion of heat exchanger tubes

Volume: 16, Issue: 7, Pages: 2382 - 2387
Published: Oct 1, 2009
Abstract
The shell and tube heat exchanger failed before 5 years of operation. The failure was caused by pits on the tube outside surface developing until its perforation. Inside the Cu-DHP tubes in soft temper a cooling agent circulated to cool down industrial water at the shell side from 16 to 4 °C. The cooled water was hard, rich in chloride ions with relatively low sulphate ions concentration and pH ranging from 4 to 7. The leaking tubes were subject...
Paper Details
Title
Erosion–corrosion of heat exchanger tubes
Published Date
Oct 1, 2009
Volume
16
Issue
7
Pages
2382 - 2387
Citation AnalysisPro
  • Scinapse’s Top 10 Citation Journals & Affiliations graph reveals the quality and authenticity of citations received by a paper.
  • Discover whether citations have been inflated due to self-citations, or if citations include institutional bias.