Punching shear strengthening of flat slabs using prestressed carbon fiber-reinforced polymer straps

Published on Oct 1, 2014in Engineering Structures3.548
· DOI :10.1016/J.ENGSTRUCT.2014.07.017
Robert Koppitz5
Estimated H-index: 5
(EPFL: École Polytechnique Fédérale de Lausanne),
Albin Kenel8
Estimated H-index: 8
,
Thomas Keller45
Estimated H-index: 45
(EPFL: École Polytechnique Fédérale de Lausanne)
Sources
Abstract
An experimental study of full-scale reinforced concrete flat slabs crosswise strengthened with prestressed carbon fiber-reinforced polymer (CFRP) straps against punching shear was performed. The effects of two strap anchoring systems and of slab thickness on punching behavior were compared. In one system the anchors were adhesively bonded to the concrete surface, while an external steel frame balanced the horizontal strap force components in the second system. Strap activation and thus strap force increments were higher in cases with either lower prestressing or higher strap stiffness. The deformability of the steel frame allowed a balancing of the strap forces. In the cases with steel frame, the friction bond between the steel anchors and the concrete surface reduced the concrete compressive zone. The system stiffness was thus increased and the rotation capacity reduced compared to the case with bonded anchors. The thickest slab exhibited a reduced rotation capacity and thus strap activation. The slab therefore failed at the lowest load increase, which however was still 67% above the theoretical resistance of the non-strengthened slab.
📖 Papers frequently viewed together
332 Citations
23 Citations
28 Citations
References29
Newest
#1Hazem A. El-Enein (U of W: University of Windsor)H-Index: 1
#2Hossein Azimi (RyeU: Ryerson University)H-Index: 6
Last. Faouzi Ghrib (U of W: University of Windsor)H-Index: 11
view all 4 authors...
Abstract The objective of this paper is to investigate experimentally the effectiveness of application of carbon fiber reinforced polymer (CFRP) sheets as a strengthening technique of a reinforced concrete (RC) slab–column connection in one-way flat-plate system to enhance its flexural strength. The experimental study was particularly conducted to examine whether there is enough anchorage with the use of CFRP wrapping to the discontinuous longitudinal CFRP sheets at column stub. Series of tests ...
11 CitationsSource
#1Thomas KellerH-Index: 45
#2Albin KenelH-Index: 8
Last. Robert KoppitzH-Index: 5
view all 3 authors...
Three different carbon fiber-reinforced polymer (CFRP) systems were used to reinforce new or strengthen existing concrete slabs against punching. Untensioned CFRP plates or only very low prestressed CFRP straps could not prevent brittle punching failure. Strap prestressing of at least 15% of the tensile strength led to a ductile two-peak slab response although the CFRP material systems were brittle. The ultimate load of the unreinforced slabs could be increased by 77 to 118% via a redistribution...
15 CitationsSource
#1Robert Koppitz (EPFL: École Polytechnique Fédérale de Lausanne)H-Index: 5
#2Albin KenelH-Index: 8
Last. Thomas Keller (EPFL: École Polytechnique Fédérale de Lausanne)H-Index: 45
view all 3 authors...
The conversion of existing buildings, development of standards, material deterioration and detailing deficiencies have led to a need for strengthening an increasing number of concrete flat slabs against brittle punching shear failure. However, existing analytical and design models do not yet take into account the specific aspects of strengthening slabs against punching shear. More than 40 models exist for predicting the punching shear strength of new slabs. A three-level classification is propos...
23 CitationsSource
#1M. Hasan Meisami (IUT: Isfahan University of Technology)H-Index: 3
#2Davood Mostofinejad (IUT: Isfahan University of Technology)H-Index: 27
Last. Hikaru Nakamura (Nagoya University)H-Index: 17
view all 3 authors...
Abstract The results of an experimental program on two-way reinforced concrete (RC) flat slabs under punching shear due to central loading are presented in this paper. All the six RC slabs were designed according to ACI 318-08 code provisions. Two slabs served as control without any modification while the other four were strengthened in different ways: one with M16 screws and nuts, and three with CFRP rods. For strengthening in each case, 8 and 24 strengtheners were used. A method is proposed fo...
37 CitationsSource
This study addresses design aspects for the punching shear bolt retrofitting system for reinforced concrete flat slabs supported on columns. Shear bolts are an external type of reinforcement installed in existing slabs by first drilling small holes through the slab thickness, installing the bolts into them, and tightening the bolt nuts. Previous experimental research at the University of Waterloo showed the effectiveness of this system in increasing strength and ductility of existing slabs, with...
14 CitationsSource
#1Andrin Herwig (Empa: Swiss Federal Laboratories for Materials Science and Technology)H-Index: 6
#2Masoud Motavalli (Empa: Swiss Federal Laboratories for Materials Science and Technology)H-Index: 43
This paper presents a new, efficient, and economic confinement technique for square reinforced concrete (RC) columns with unbonded glass fiber-reinforced polymer (GFRP) wrapping and lightweight concrete elements at the side faces. Three confined columns with different reinforcement ratios were tested under concentric axial force. The force-deformation responses show a distinctly increased load-carrying capacity at plastic deformations up to 4% average axial strain. This confinement technique is ...
17 CitationsSource
#1Stefan LipsH-Index: 3
Last. Aurelio MuttoniH-Index: 32
view all 3 authors...
This paper presents the results of an extensive experimental campaign on 16 flat-slab specimens with and without punching shear reinforcement. The tests aimed to investigate the influence of a set of mechanical and geometrical parameters on the punching shear strength and deformation capacity of flat slabs supported by interior columns. All specimens had the same plan dimensions of 3.0 x 3.0 m (9.84 x 9.84 ft). The investigated parameters were the column size (ranging between 130 and 520 mm [app...
85 CitationsSource
#1Duarte M. V. Faria (NOVA: Universidade Nova de Lisboa)H-Index: 10
#2Valter José da Guia Lúcio (NOVA: Universidade Nova de Lisboa)H-Index: 10
Last. A. Pinho Ramos (NOVA: Universidade Nova de Lisboa)H-Index: 7
view all 3 authors...
Abstract This work presents an experimental study concerning the post-punching behaviour of flat slabs strengthened with a new technique based on post-tensioning with anchorages by bonding using an epoxy adhesive. This strengthening technique proved efficient with respect to ultimate and serviceability states. Five slab specimens were tested in the post-punching range and it was found that the post-punching resistance was on average 78% of the punching resistance. This paper reports the developm...
8 CitationsSource
#1T El-ShafieyH-Index: 1
#2A AttaH-Index: 1
2 CitationsSource
#1Nicholas Lawler (UW: University of Waterloo)H-Index: 2
#2Maria Anna Polak (UW: University of Waterloo)H-Index: 22
A fiber-reinforced polymer (FRP) shear bolt system has been recently developed at the University of Waterloo in Canada. The system is used to protect previously built reinforced concrete (RC) slabs against brittle punching shear failure. The system requires drilling small holes in a RC slab around the perimeter of a column, inserting bolts into the holes, and anchoring the bolts at both external surfaces of the slab. Many existing RC slabs have been built without any shear reinforcement. Also, m...
18 CitationsSource
Cited By18
Newest
Abstract null null To reinforce the inclined web shear crack in the shear span of the prestressed concrete hollow slab beam (PCHSB) on a bridge running for 20 years, a new method of grouting reinforcement was developed. Meanwhile, the grouting material corresponding to this method was developed, so as to improve the shear bearing capacity of prestressed concrete hollow slab. To verify the mechanical performance and reinforcement effect of the strengthened PCHSB, the shear resistance tests were c...
Source
Abstract This paper presents the effectiveness of strengthening slab–column connections against punching shear failure with near surface–mounted (NSM) carbon fiber–reinforced polymer (CFRP) bars. T...
Source
#1Rupert Walkner (University of Innsbruck)H-Index: 2
#2Matthias Spiegl (University of Innsbruck)H-Index: 2
Last. Jürgen Feix (University of Innsbruck)H-Index: 4
view all 3 authors...
Source
#1H.R. Taresh (UKM: National University of Malaysia)
#2Mohd. Yazmil Md. Yatim (UKM: National University of Malaysia)H-Index: 3
Last. Mohd Reza Azmi (UKM: National University of Malaysia)H-Index: 1
view all 3 authors...
Abstract The present paper is concerned with a series of tests on reinforced concrete flat slabs to examine the behaviour of interior slab-column connections employing steel angle plates and high strength bolts as strengthening elements. The angle plates were bolted to the column faces and slab at both tension and compression sides. The shorter leg of the angle plate attached to the column face acts as a column capital of an equivalent concrete width whilst the longer leg is treated as a drop pa...
Source
Abstract In recent years, strengthening through using fibre reinforcing polymer (FRP), has been widely used in buildings, especially slab-column connections. This is due to several reasons; such as the application of additional loads, incorrect analysis and design and others. There are many standards to deal with the FRP application. Each standard has its own specification, which differs from others. No comparison between the standards has been conducted to advise the designer to choose his suit...
Source
#1Takafumi Mihara (Yamaguchi University)H-Index: 2
#2Isamu Yoshitake (Yamaguchi University)H-Index: 10
Last. Tatsuhiko MimotoH-Index: 2
view all 5 authors...
Abstract The present study focused on creation of an internal strengthening system, which involved embedding a post-tensioned PC tendon in a wedge-shaped anchorage of an existing concrete member. Under conditions with narrow work spaces, it was difficult to employ the previous system using a post-tensioned prestressing bar, as adequate backspace was required to install the bar. A flexible hollow corrugated pipe covered with steel wire cables seemed applicable even in such narrow spaces. Interest...
1 CitationsSource
Abstract This paper presents an experimental research program on the punching strengthening of flat reinforced concrete (RC) slabs with carbon fibre reinforced polymer (CFRP) systems. The strengthening system consists of CFRP wet layup sheets that are installed into holes opened orthogonally to the RC slab, and bonded to the surrounding substract with epoxy adhesive. Two different techniques were adopted: one where the CFRP system fully wraps two consecutive holes, forming a close type stirrup; ...
2 CitationsSource
#1Xiangguo Wu (HIT: Harbin Institute of Technology)H-Index: 2
#2Shi-yan Yu (HIT: Harbin Institute of Technology)H-Index: 1
Last. Hyeon-Jong Hwang (Hunan University)H-Index: 12
view all 5 authors...
Abstract Reinforced concrete (RC) flat plates are vulnerable to punching shear failure due to small effective area for shear resistance. To strengthen the behavior of existing flat plates, use of ultra high performance fiber reinforced concrete (UHPFRC) as a laminate has been pursued. This study focuses on punching shear behavior of RC flat plates retrofitted with UHPFRC overlay (i.e., UHPFRC-RC composite flat plates). To model the axisymmetric UHPFRC-RC composite flat plate, use of the unified ...
3 CitationsSource
#1Massimo Lapi (UniFI: University of Florence)H-Index: 5
#2Antonio Ramos (Faculdade de Ciências e Tecnologia da Universidade Nova de Lisboa)H-Index: 43
Last. Maurizio Orlando (UniFI: University of Florence)H-Index: 13
view all 3 authors...
Abstract Over the years, the flat slab system has become a popular form of construction in many countries, particularly for multi-storey buildings such as offices or carparks. Nowadays, a considerable number of flat slab buildings requires strengthening against punching. Reasons are several, like design or construction errors, poor quality materials, not complying with new codes provisions, or increase of vertical load. This paper discusses different techniques for strengthening of R/C slabs aga...
16 CitationsSource
#1Panatchai Chetchotisak (Rajamangala University of Technology)H-Index: 3
#2Pongpan Ruengpim (Rajamangala University of Technology)H-Index: 1
Last. Sukit Yindeesuk (MTO: Ontario Ministry of Transportation)H-Index: 3
view all 4 authors...
Based on a database of 342 experimental results with a wide range of influencing parameters, a new empirical model was developed using Multiple Linear Regression (MLR) for predicting the concentric punching shear strength of RC slab-column connections, without shear reinforcement, and was presented in this paper. An Artificial Neural Network (ANN) and international codes of practice as well as a state-of-the-art approach were also employed for comparison purpose. To avoid the over-fitting proble...
6 CitationsSource